SAMPLE — NOT FOR JOBSITE USE
Torch-applied roofing JHA Example
This educational roofing example is generated from source-mapped clause bank version 2026.08.28-ai3.
| Clause | Control | Citation |
|---|---|---|
| CTL-FALL-001 | Employees on walking or working surfaces with unprotected sides or edges 6 feet or more above a lower level shall be protected by guardrail systems, safety net systems, or personal fall arrest systems unless a specific Subpart M alternative applies. | 29 CFR 1926.501(b)(1) |
| CTL-FALL-002 | Personal fall arrest systems shall be inspected before each use for wear, damage, and other deterioration, and defective components shall be removed from service. | 29 CFR 1926.502(d)(21) |
| CTL-FALL-004 | Anchorages used for attachment of personal fall arrest equipment shall be independent of any anchorage being used to support or suspend platforms and capable of supporting at least 5,000 pounds per employee attached, or shall be designed, installed, and used as part of a complete personal fall arrest system that maintains a safety factor of at least two, under the supervision of a qualified person. | 29 CFR 1926.502(d)(15) |
| CTL-HEAT-001 (recommended practice) | The employer heat-illness prevention plan should account for heat conditions and workload; provide adequate cool drinking water, rest breaks, and a shaded or cool recovery area; gradually acclimatize new and returning workers; train workers and supervisors to recognize and respond to heat illness; and require 911 activation with immediate aggressive cooling for suspected heat stroke. | Recommended practice OSH Act Section 5(a)(1); OSHA Heat Exposure prevention guidance |
| CTL-FIRE-001 | Suitable fire-extinguishing equipment shall be immediately available in the work area and shall be maintained in a state of readiness for instant use. | 29 CFR 1926.352(d) |
| CTL-FIRE-002 | When a welding, cutting, or heating operation (including torch-applied roofing) is such that normal fire prevention precautions are not sufficient, additional personnel shall be assigned to guard against fire while the work is in progress and for a sufficient period after completion to ensure that no possibility of fire exists; such personnel shall be instructed in the anticipated fire hazards and in how the fire-protection equipment is to be used. | 29 CFR 1926.352(e) |
| CTL-FIRE-003 | When practical, objects to be welded, cut, or heated shall be moved to a designated safe location; if they cannot readily be moved, all movable fire hazards in the vicinity shall be taken to a safe place or otherwise protected; where the object cannot be moved and the fire hazards cannot all be removed, positive means shall be taken to confine the heat, sparks, and slag and to protect the immovable fire hazards from them. | 29 CFR 1926.352(a); 29 CFR 1926.352(b) |
| CTL-FIRE-004 | Where a welding, cutting, or heating operation is performed on one side of a wall, partition, ceiling, or roof, precautions shall be taken to prevent ignition of combustibles on the other side, and where combustibles cannot be relocated, a fire watch shall be posted on the opposite side. | 29 CFR 1926.352(f) |